Electro Cables
Login
  • Products
  • Custom Cable
  • Inventory
  • About
  • Careers
  • Contact
Electro Cables

Have a question? Contact us at 1 (888) 353-2876

Login
  • Products
  • Custom Cable
  • Inventory
  • About
  • Careers
  • Contact

PRODUCTS

A partner you can trust

  

Browse Products

Building & Industrial

Component Cable

Electronic Cables

Category Cable

Transit & Railway Cable

Custom Cable

CIC Shielded Pairs & Triads▸

AC90▸

Copper Conductors 600V▸

Aluminum Conductors 600V▸

ACWU90▸

Aluminum Conductors 600V▸

Copper Conductors 600V▸

TECK90▸

Copper Conductors 600V▸

Copper Conductors 1000V▸

Aluminum Conductors 1000V▸

TECK90 Vertical Riser▸

Copper Conductors 1000V▸

Aluminum Conductors 1000V▸

Lighting Power & Control▸

TRAY CABLE TC▸

Control Copper Conductors▸

CIC Unshielded Multi-Conductor 600V▸

CIC Shielded Multi-Conductor 600V▸

Power Copper Conductors▸

RW90 600V▸

RW90 1000V▸

TRAY CABLE TC-ER▸

Power Copper Conductors▸

RW90 600V▸

RW90 1000V▸

Control & Instrumentation Cable▸

ACIC Shielded Pairs & Triads▸

ACIC ELCON® Non-Shielded Multi-Conductor▸

RW90▸

COPPER CONDUCTORS 600V▸

COPPER CONDUCTORS 1000V▸

ALUMINUM CONDUCTORS 600V▸

RWU90▸

COPPER CONDUCTORS 1000V▸

ALUMINUM CONDUCTORS 1000V▸

Solar / Photovoltaic Cable▸

NMD90▸

NMWU90▸

TW75▸

TWU▸

Bare Wire▸

FIRE ALARM ARMOURED▸

RED ARMOURED▸

SILVER ARMOURED▸

FIRE ALARM UNARMOURED▸

FAS FT4 CSA▸

FPLR CMR UL▸

TEW FT1 CSA | AWM MTW VW1 UL▸

TR-64 FT1 CSA | AWM VW1 UL▸

Low Voltage Thermostat▸

Speaker Wire▸

Irrigation▸

Tracer▸

CMG AWM FT4 CSA | CMG UL▸

Unshielded▸

Overall Foil Shield▸

CMP FT6 CSA | CMP PLENUM UL▸

LOW CAPACITANCE CABLE▸

STATION Z / QUAD CABLE▸

Cat 6 - 1 Cable▸

Cat 6 - 2 Cables▸

Cat 6 - 4 Cables▸

Traffic Signal▸

CP-100▸

MTOIMSACP-100ISO-SPC90 600VSPC90 600VTWU 600V 14 AWG - 4 AWGTW75 600V 12 AWG - 4/0 AWGCMP FT6 CSACMR RISER UL CMG FT4 CSA4 Conductor 6 AWG - 750 kcmil3 Conductor 6 AWG - 750 kcmil1 Conductor 6 AWG - 750 kcmil4 Conductor 6 AWG - 750 kcmil3 Conductor 6 AWG - 750 kcmil1 Conductor 8 AWG - 750 kcmil4 Conductor 6 AWG - 750 kcmil4 Conductor 6 AWG - 750 kcmil3 Conductor 6 AWG - 750 kcmil1 Conductor 14 AWG - 1000 kcmil1 Conductor 14 AWG - 1000 kcmil3 Conductor 6 AWG - 750 kcmil1 Conductor 8 AWG - 750 kcmilRPVU90 Copper 2000VRPVU90 Aluminum 2000VRPV90 Copper 600VRPV90 Copper 2000V16 AWGNMD90 Aluminum 300V 8 AWG - 2 AWGNMD90 Copper 300V 8 AWG - 2 AWGCMP FT6 CMG FT4 1 Conductor 8 AWG - 1000 kcmil10 AWG 2 - 50 Conductor12 AWG 2 - 50 Conductor14 AWG 2 - 50 Conductor1 Conductor 8 AWG - 1000 kcmil4 Conductor 8 AWG - 750 kcmil3 Conductor 8 AWG - 750 kcmil 2 Conductor 8 AWG - 750 kcmil 1 Conductor 8 AWG - 1000 kcmil14, 12 and 10 AWG 2 - 50 Conductor14, 12 and 10 AWG 2 - 50 Conductor1 Conductor 8 AWG - 1000 kcmil16 AWG 300V16 AWG 2 - 50 Conductor18 AWG 300V18 AWG14 AWG to 10 AWG20 AWG to 12 AWG300V Tinned Copper16 AWG & 18 AWG600V Bare Copper 22 AWG - 10 AWG600V Tinned Copper 22 AWG - 10 AWGIn-Wall and Parallel14 AWG & 12 AWG 2 - 4 Conductor16 AWG 2 - 4 Conductor18 AWG 2 - 12 Conductor12 AWG Red12 AWG Silver16 AWG Red 3 - 5 Conductor14 AWG Red 3 - 5 Conductor16 AWG Silver 3 - 5 Conductor14 AWG Silver 3 - 5 Conductor18 AWG Red 3 - 9 Conductor18 AWG Silver 3 - 9 Conductor12 AWG16 AWG 3 - 5 Conductor14 AWG 3 - 5 Conductor18 AWG 3 - 50 Conductor10 AWG 2 - 50 ConductorCAT6 X4 F/UTP Shielded Armoured12 AWG 2 - 50 ConductorCAT6 X2 F/UTP Shielded Armoured14 AWG 2 - 50 ConductorV-TECK 4 ConductorCAT6e U/UTP Unshielded ArmouredCAT6 F/UTP Shielded ArmouredV-TECK 3 Conductor4 Conductor 8 AWG - 1000 kcmil3 Conductor 8 AWG - 1000 kcmil2 Conductor 14 AWG - 500 kcmil1 Conductor 250 kcmil - 1500 kcmilV-TECK 4 ConductorV-TECK 3 Conductor4 Conductor 4 AWG - 750 kcmil3 Conductor 4 AWG - 750 kcmil1 Conductor 250 kcmil - 1000 kcmilBare Copper Wire 20 AWG - 350 kcmil4 Conductor 6 AWG - 750 kcmil3 Conductor 6 AWG - 1000 kcmil1 Conductor 1/0 AWG - 1000 kcmilSingle and Multi-conductorsISO-AC904 Conductor3 Conductor2 Conductor (Black/Red)2 Conductor (Black/White)4 ConductorCUSTOM CABLE3 Conductor16 AWG 600V18 AWG 600V16 AWG 300V18 AWG 300VNMWU90 300V 8 AWG - 2 AWG20 AWG22 AWG14 AWG16 AWG18 AWG22 AWG20 AWG24 AWG14 AWG16 AWG18 AWG20 AWG22 AWG24 AWG
Home > Shop > Building & Industrial > TRAY CABLE TC-ER > Power Copper Conductors > RW90 1000V > RW90 TC-ER Tray Cable 1000V – XLPE/PVC 3 Conductor Copper

ElectroPower®®

PRODUCT PDF
CHECK INVENTORY
VIEW QUOTE

RW90 TC-ER Tray Cable 1000V – XLPE/PVC 3 Conductor Copper

Temperature Range:

CSA Type XL 90°C dry/wet 1000V

Conductor:

Stranded Soft Bare Copper, ASTM B8

Insulation:

Cross-linked Polyethylene (XLPE) CSA Type XL 90°C dry/wet 600V

Colour Code:

Black & White or Black with White printed number

Bonding Conductor:

Green Insulated Stranded Bare Soft Copper, ASTM B8

Jacket:

Low Acid Gas Polyvinyl Chloride (PVC)

  • RW90

  • FLAME
    RATING

  • LOW
    TEMP

  • HIGH
    TEMP

  • UV
    Resistant

  • WET
    LOCATION

  • Chemical
    Resistant

  • Oil
    Resistant

  • Impact
    Resistant

  • TRAY
    CABLE (TC)

  • Exposed
    Run

  • DIRECT
    BURIAL

  • Tray Cable

  • Hazardous
    Location

Specifications and Compliance:

  • CSA C22.2 No. 38 Thermoset-Insulated Wires and Cables Type RW90
  • CSA C22.2 No. 230, Tray Cables
  • CSA C22.2 No. 2556 FT4, IEEE 1202/UL 1865 Vertical-Tray Flame Test
  • -40°C Cold Bend and -40°C Cold Impact
  • Sunlight Resistant, SUN RES

Applications:

For use in raceways, including cable trays, Ventilated, nonventilated, ladder tray and direct burial.

To be used for exposed and concealed wiring or where subjected to the weather.

For Hazardous Locations Class I-Zone 0 Intrinsically safe Div. 2, Class II-Zone 2 Div. 2 and Class III-Div. 2.

Cables marked TC-ER tray cable are permitted to transition between cable trays, and utilization equipment or devices as per CEC Part I 12-2202 2) and 3).

To add or modify your quote request, please log in

Available Options:

  • Additional information

Additional information

PART NO.

8210803BBG-P4E, 8210603BBG-P4E, 8210403BBG-P4E, 8210303BBG-P4E, 8210203BBG-P4E, 8210103BBG-P4E, 82101/003BBG-P4E, 82102/003BBG-P4E, 82103/003BBG-P4E, 82104/003BBG-P4E, 82125003BBG-P4E, 82130003BBG-P4E, 82135003BBG-P4E, 82140003BBG-P4E, 82150003BBG-P4E, 82160003BBG-P4E, 82175003BBG-P4E

POWER CONDUCTOR SIZE

8, 6, 4, 3, 2, 1, 1/0, 2/0, 3/0, 4/0, 250, 300, 350, 400, 500, 600, 750

BONDING CONDUCTOR SIZE

10, 8, 8, 6, 6, 6, 6, 6, 4, 4, 4, 4, 3, 3, 2, 2, 2

INSULATION THICKNESS

0.045 in. ~ 1.14 mm, 0.060 in. ~ 1.52 mm, 0.080 in. ~ 2.03 mm, 0.090 in. ~ 2.28 mm

JACKET THICKNESS

0.060 in. ~ 1.5 mm, 0.080 in. ~ 2.0 mm, 0.110 in. ~ 2.8 mm, 0.140 in. ~ 3.6 mm

CABLE O.D.

0.630 in. ~ 16.0 mm, 0.777 in. ~ 19.7 mm, 0.937 in. ~ 23.8 mm, 1.000 in. ~ 25.4 mm, 1.067 in. ~ 27.1 mm, 1.205 in. ~ 30.6 mm, 1.280 in. ~ 32.5 mm, 1.364 in. ~ 34.7 mm, 1.462 in. ~ 37.1 mm, 1.604 in. ~ 40.7mm, 1.828 in. ~ 46.4 mm, 1.944 in. ~ 49.4 mm, 2.079 in. ~ 52.8 mm, 2.133 in. ~ 54.2 mm, 2.335 in. ~ 59.3 mm, 2.423 in. ~ 61.6 mm, 2.881 in. ~ 73.2 mm

CABLE WEIGHT

339 lbs/Mft ~ 504 kg/km, 491 lbs/Mft ~ 730 kg/km, 710 lbs/Mft ~ 1057 kg/km, 856 lbs/Mft ~ 1275 kg/km, 1008 lbs/Mft ~ 1500 kg/km, 1271 lbs/Mft ~ 1892 kg/km, 1525 lbs/Mft ~ 2270 kg/km, 1802 lbs/Mft ~ 2682 kg/km, 2228 lbs/Mft ~ 3316 kg/km, 2698 lbs/Mft ~ 4015 kg/km, 3340 lbs/Mft ~ 4971 kg/km, 3883 lbs/Mft ~ 5778 kg/km, 4479 lbs/Mft ~ 6666 kg/km, 4996 lbs/Mft ~ 7434 kg/km, 6115 lbs/Mft ~ 9100 kg/km, 7147 lbs/Mft ~ 10637 kg/km, 8975 lbs/Mft ~ 13357 kg/km

MAX. PULLING TENSION

454 lbs ~ 206 kg, 629 lbs ~ 286 kg, 1001 lbs ~ 455 kg, 1263 lbs ~ 574 kg, 1594 lbs ~ 724 kg, 2010 lbs ~ 914 kg, 2531 lbs ~ 1150 kg, 3195 lbs ~ 1452 kg, 4029 lbs ~ 1831 kg, 5075 lbs ~ 2307 kg, 6000 lbs ~ 2727 kg, 7193 lbs ~ 3269 kg, 8407 lbs ~ 3821 kg, 9605 lbs ~ 4366 kg, 11990 lbs ~ 5450 kg, 14407 lbs ~ 6548 kg, 18005 lbs ~ 8184 kg

MIN. BEND RADIUS

7.6 in. ~ 192 mm, 9.3 in. ~ 237 mm, 11.2 in. ~ 286 mm, 12.0 in. ~ 305 mm, 12.8 in. ~ 325 mm, 14.5 in. ~ 367 mm, 15.4 in. ~ 390 mm, 16.4 in. ~ 416 mm, 17.5 in. ~ 446 mm, 19.3 in. ~ 489 mm, 21.9 in. ~ 557 mm, 23.3 in. ~ 593 mm, 25.0 in. ~ 634 mm, 25.6 in. ~ 650 mm, 28.0 in. ~ 712 mm, 29.1 in. ~ 739 mm, 34.6 in. ~ 878 mm

AMPACITY (A)

55, 75, 95, 115, 130, 145, 170, 195, 225, 260, 290, 320, 350, 380, 430, 475, 535

Related products

  • RW90 TC-ER Tray Cable 1000V – XLPE/PVC 2 Conductor Copper

    $0.00
    Select options
  • RW90 TC-ER Tray Cable 1000V – XLPE/PVC 4 Conductor Copper

    $0.00
    Select options
  • RW90 TC-ER Tray Cable 1000V XLPE/PVC – 1 Conductor Copper

    $0.00
    Select options
VIEW QUOTE () ADD TO QUOTE

For specifications, please contact our sales team at 1-888-ELECTRO (613-394-4896) or sales@electrocables.com.

Options

This cable is also available with the following options. For more information, please contact sales@electrocables.com or call 1-888-353-2876.

  • FLAME
    RATING

  • Limited
    SMOKE

  • Halogen
    Free

X

Invalid user name or password

Register Now Forgot your password?

Products

Products

LEARN MORE

Products

Current Inventory

Current Inventory

LEARN MORE

Current Inventory

Custom Solutions

Custom Solutions

WE CAN HELP

Custom Solutions

Lighting Power & Control-Signal Cable

This content is restricted to site members. If you are an existing user, please log in. New users may register … LEARN MORE “Lighting Power & Control-Signal Cable”

LOOKING
FOR HELP?

We are here to help. You can contact us or create an account online to have access to special products, technical specifications and our new online quote tool.

GET IN TOUCH

ELECTRO CABLES

9 Riverside Drive
P.O. Box 276
Trenton, Ontario
CANADA K8V 5R5

N.A. Toll Free: 888-ELECTRO
(1-888-353-2876)

World: 613-394-4896

Fax: 613-394-4101

Email: sales@electrocables.com

We manufacture cables that are certified by the Canadian Standards Association (CSA), listed by Underwriters Laboratories and/or listed by Intertek (ETL).

Our quality management system is registered to ISO 9001: 2015. Our team is dedicated to consistently providing quality service and products to our customers.

 SCROLL UP