Additional information
| PART NO. | 6XAAUS14-2C-IS-16-2C, 6XAAUS12-2C-IS-16-2C, 6XAAUS10-2C-IS-16-2C |
|---|---|
| NO. POWER CONDUCTOR | 2 |
| POWER CONDUCTOR SIZE | 14 AWG, 12 AWG, 10 AWG |
| INSULATED BONDING CONDUCTOR SIZE | 14 AWG, 12 AWG, 10 AWG |
| BARE BONDING CONDUCTOR SIZE | 14 AWG, 12 AWG |
| NO. CONTROL CONDUCTOR | 2 |
| CONTROL CONDUCTOR SIZE | 16 AWG |
| ARMOUR O.D | 0.595 in. ~ 15.2 mm, 0.640 in. ~ 16.3 mm, 0.685 in. ~ 17.8 mm |
| CABLE WEIGHT | 124 lbs/Mft ~ 184 kg/km, 144 lbs/Mft ~ 215 kg/km, 205 lbs/Mft ~ 305 kg/km |
| MAX. PULLING TENSION | 131 lbs ~ 60 kg, 209 lbs ~ 95 kg, 332 lbs ~ 151 kg |
| MIN. BEND RADIUS | 7.1 in ~ 181 mm, 7.7 in. ~ 195 mm, 8.2 in. ~ 208 mm |
| AMPACITY (A) | 25, 30, 40 |